Gas Detectors SGOES, SGOES-2 (hereinafter SGOES) monitors concentration of hydrocarbon gases in the environment and measures explosive consentrations of methane, propane, butane, iso-butane, pentane, hexane, heptane, ethane, ethylene, propylene, acetone vapors, benzene, ethyl benzene, toluene, xylene, methyl tertiary butyl ether, ethyl, methyl and isopropyl alcohol mixed with nitrogen or air, and also for gas control work area actual pairs employed industrial petroleum products (gasoline, kerosene, diesel fuel, mineral spirits, etc.) SGOES analyzers are available in explosion-proof and certified for use in hazardous locations. SGOES used in automated alarm systems or as a stand-alone gas detectors for combustible gases and vapors.

  • Oil platforms
  • Tankers for the transport of oil, cargo ships and vessels
  • Companies producing liquefied natural gas storage / liquefied gas
  • Compressor stations
  • Petrochemical and thermal power stations
  • Gas turbines
  • Oil and gas pipelines
  • Transport companies (airports and subways)
  • Oil and gas boilers and furnaces
  • Pumping oil and gas pipelines, tank farms

NameValues
Model SGOES
Enclosure Al alloy 
Ex marking 1 Exd IIC T4 Gb
IP protection IP 66
Overall dimensions of SGOES370 × 190 × 120.
Wight of SGOES4‚2
Cable entry М20
Temperature range SGOES SGOES-2 from -60 to+85 °C   from -60 to +90 °C
Relative humidity Up to 100% (without condensation) 
Power supply  Nominal-  24 VDC Range 18 …32 VDC 
Power consumption of SGOES5‚5 W 
Output signals - analog signal: 4..20 mА;

- digital signals RS-485 with interface Modbus RTU;

- dry contact relays «Exceeding of gas level » и «Faulty».

Warming time 

Not more then 10 minutes 
The limits of permissible variation indication outputs SGOESno more than 0.5 shares of the limits of basic error
Changing the output of analog and digital signals SGOESno more than 0.5 shares of the limits of basic error;
Average time to establish the output of analog and digital signals SGOES1T0‚9 – 20 sec.; T0‚5 – 10 sec
Reading range 0 ÷ 100 % LEL 
Seismic SGOESunder the influence of earthquake intensity of 9 points on MSK 64 at installation level above ground level to 10 meters according to GOST 30546.1-98. 
Limits of additional error from ambient temperature changes for every 10 ° C in the range from -60 to 85 ° C no more than 0.5 shares of the limits of basic error 
Warrantee 2 years 
Average life 15 years 
MTBF То  Not less 35 000 hours    

 

C-42, Okhla Industrial Area Phase-II, New Delhi 110020, INDIA
Phone:  +91 11 41328005

e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.

e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.

Unit No: 710; Exim Link Complex, Goregaon Link Road, Opposite Indira Container Yard, Nahur-Bhandup (W) Mumbai - 400 078.

Phone:  +91 93 24727788         +91 22 67082735

e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.

This email address is being protected from spambots. You need JavaScript enabled to view it.

Top